Commercial Carpet Fire Ratings in Australia, Explained

Updated 16 November 2026
Before carpet can go into most commercial buildings in Australia, it has to pass a fire test. The test gives the carpet a fire score, officially called critical radiant flux (CRF). The higher the score, the harder it is for fire to spread across the floor. Most offices need a score of at least 2.2, or 1.2 if the building has sprinklers. Aged care and hospital patient areas can need 4.5. Apart from one cushion-back Aura colour, all 17 of our ranges with their own fire test score 4.5 or higher.
The short version
- Fire score (critical radiant flux): higher is better. You need 1.2, 2.2 or 4.5, depending on the building.
- Smoke score (smoke development rate): lower is better. It must be 750 or less in buildings without sprinklers.
- Where the rule comes from: the National Construction Code (NCC), Specification 7, clause S7C3. It’s the same in NCC 2022 and NCC 2025.
- How it’s tested: the Australian floor fire test, AS ISO 9239.1.
- Our ranges: all 17 of our ranges with their own fire test score 4.5 or higher, so each one clears even the strictest requirement. The one exception is the Aura colour Dusk, a cushion-back tile, at 3.9.
How the fire test works
A strip of flooring is laid flat under a heater that is very hot at one end and cooler at the other. The flooring is lit at the hot end, and the flame creeps along it until the heat is too low for it to keep burning.
Where the flame stops gives the fire score. If the flame stops early, while the heat is still high, the score is high: the flooring needs a lot of heat before fire can spread across it. The score is measured in kW/m², but you only need to know that a bigger number is safer.
The same test also measures the smoke the flooring gives off. That’s the smoke score, in percent-minutes. Less smoke means a lower, better score.
What score do you need?
It depends on two things: what the building is used for, and whether it has sprinklers.
| Where the flooring is going | Fire score needed |
|---|---|
| Offices, shops, schools, apartments and most public buildings, with sprinklers | 1.2 or more |
| The same buildings without sprinklers | 2.2 or more |
| Aged care and hospital patient areas without sprinklers, and fire exits in those buildings | 4.5 or more |
In any building without sprinklers, the smoke score must also be 750 or less.
Your building certifier confirms which of these applies to each project. Specifiers can find the full NCC table, with every building class, further down this page.
How our ranges score
Every range below scores 4.5 or more, so it meets the highest fire score in the NCC. Every smoke score is far below the 750 limit.
| Range | Type | Fire score (higher is better) | Smoke score (lower is better) |
|---|---|---|---|
| Flinders | Vinyl plank | 10.7 | 41 |
| Blur | Carpet tile | 9.4 | 42 |
| Australian Stone Collection | Vinyl tile | 9.3 | 75 |
| Habitat Rhomb | Carpet tile | 8.2 | 52 |
| New Forest | Vinyl plank | 8.1 | 250 |
| Quartz | Carpet tile | 7.6 | 26 |
| Nostalgic | Carpet tile | 7.1 | 21 |
| Guniimaa Collection | Carpet tile | 6.8 | 43 |
| Dynamic | Carpet plank | 6.8 | 32 |
| Aura | Carpet tile (except Dusk, see below) | 6.4 | 37 |
| Linear | Carpet tile | 6.4 | 77 |
| Mist | Carpet tile | 6.1 | 33 |
| Stonewall | Carpet plank | 5.7 | 167 |
| Knit | Carpet tile (cushion back) | 5.3 | 75 |
| Water Shallow | Carpet plank | 4.9 | 207 |
| The Ultimate | Carpet tile | 4.7 | 165 |
| Austral Lights | Carpet tile | 4.5 | 110 |
What these numbers mean for your project:
- Any of these ranges can go into offices, shops, schools and public buildings, with or without sprinklers.
- Any of these ranges also meets the 4.5 needed in aged care, hospital patient areas and fire exits.
- All smoke scores are under 750, so every range suits buildings without sprinklers too.
- One exception: Aura in Dusk. Dusk is a cushion-back tile and scores 3.9. It suits offices and most buildings (2.2 or more), but not areas that need 4.5.
A score applies to the exact product and backing that was tested. If you’re choosing a different backing, such as a cushion back, ask us for the matching report. The full test report for every range is on its range page, under Product Info and Downloads.

Real projects
- Aged care: Stonewall carpet planks in Riverstone at Catholic Aged Care in Wahroonga. Stonewall scores 5.7, above the 4.5 needed in the strictest aged care areas.
- Health: The Ultimate in Alaska at the Wesfarmers Health support office in South Australia, and Stonewall in Clay at a physiotherapy clinic in Redfern.
- Libraries: Aura in Mood and Affinity at Moree Library. Aura scores 6.4, well above the 2.2 a library usually needs.

Three things to check on every job
- Does the building have sprinklers? No sprinklers means a higher fire score and a smoke limit.
- Is any flooring going into a fire exit? Fire-isolated stairs and passageways need 2.2 or 4.5, even with sprinklers.
- Is the report for the exact product? A cushion-back version of a tile can score differently from the standard one.
One more tip: carpet doesn’t have a “Group 1” rating. Group numbers are for walls and ceilings. Floors use the fire score, unless the carpet runs more than 150 mm up a wall.
Frequently asked questions
What fire rating does commercial carpet need in Australia?
Most offices, shops and schools need a fire score (critical radiant flux) of at least 2.2 kW/m², or 1.2 with sprinklers. Aged care and hospital patient areas without sprinklers, and fire exits in those buildings, need 4.5.
What is critical radiant flux?
It’s the fire score from the Australian floor fire test, AS ISO 9239.1. It shows how much heat it takes for fire to keep spreading across the flooring. A higher number is safer.
Do carpet tiles have a Group 1 fire rating?
No. Group numbers are for walls and ceilings. Floors are rated by critical radiant flux and smoke. A group number only applies if carpet runs more than 150 mm up a wall.
What smoke rating does commercial carpet need?
In a building without sprinklers, the smoke score (smoke development rate) must be 750 percent-minutes or less. With sprinklers, there’s no smoke limit for floors.
Are Inspired Floorcoverings carpet tiles suitable for aged care?
Yes, with one exception. Our carpet ranges score between 4.5 and 9.4, so they meet the 4.5 needed in the strictest aged care areas. The exception is Aura in Dusk, a cushion-back tile that scores 3.9. Check the report for the exact product and backing, and confirm the building’s requirements with your certifier.
Where can I get the fire test report for a range?
Every range page has the full report under Product Info and Downloads. Your Inspired Floorcoverings representative can also send you a copy.
For specifiers: full NCC table and test reports
The full NCC Table S7C3 lists the minimum critical radiant flux (kW/m²) for every building class.
| Building class | No sprinklers | With sprinklers | Fire-isolated exits and fire control rooms |
|---|---|---|---|
| Class 2, 3, 5, 6, 7, 8 and most 9b | 2.2 | 1.2 | 2.2 |
| Class 3 accommodation for the aged | 4.5 | 2.2 | 4.5 |
| Class 9a patient care areas | 4.5 | 2.2 | 4.5 |
| Class 9a other areas | 2.2 | 1.2 | 4.5 |
| Class 9b indoor pools and ice rinks, audience seating | 1.2 | 1.2 | 2.2 |
| Class 9b other sports and multi-purpose, audience seating | 2.2 | 1.2 | 2.2 |
| Class 9c resident use areas | Must be sprinklered | 2.2 | 4.5 |
| Class 9c other areas | Must be sprinklered | 1.2 | 4.5 |
Our results are from AS ISO 9239.1 tests by independent laboratories accredited to ISO/IEC 17025, with most ranges tested glued to fibre cement board. Report numbers: Blur 25-000047, Habitat Rhomb 25-000050, Quartz 25-000051, Nostalgic 25-000053, Guniimaa 26-001281, Dynamic 24-004647, Aura 24-003497, Linear 24-005142, Mist 23-004418, Stonewall 24-004350, Knit 23-000871, Water Shallow 24-004645, The Ultimate 7-594146-AN, Austral Lights 17-002764, Australian Stone Collection 23-001248, New Forest 21-002677, Flinders FNR 12046C.
Next step
Browse our stock carpet tile ranges, indent designer ranges and vinyl ranges, each with its fire test report, or request free samples. For help choosing flooring for each area of an office, read Carpet Tiles or LVT for Your Office?
This guide explains the NCC in general terms. Always confirm the requirements for a specific building with your building certifier.